Wide-Temperature Managed Switch With Gigabit Uplinks
The MOXA EDS-4008-2GT-2GS-HV-T Managed Ethernet Switch combines four Fast Ethernet copper ports with two Gigabit copper ports and two SFP slots for uplinks. It adds ring redundancy and network management to an industrial network, runs from a high-voltage AC or DC supply, and works over a wide operating temperature range. Rockford Communication Solutions supplies this model to customers in Qatar.
Gigabit Copper and SFP Uplinks on an HV Power Module
This switch is the wide temperature version of a managed switch for industrial networks. It joins Fast Ethernet copper devices to a Gigabit backbone. The uplink can use the Gigabit copper ports or SFP modules, so both copper and fiber links are possible. Power comes from a single high-voltage AC or DC input. The metal housing has a compact design for confined spaces and DIN-rail cabinets, and the extended temperature range suits harsher cabinet conditions. In Industrial Network Infrastructure, it acts as the point where device-level copper links meet the backbone.
Turbo Ring Redundancy, MXstudio and Port Security
- Turbo Ring and Turbo Chain: MOXA ring and chain redundancy restores traffic after a link failure. RSTP, STP, MRP, ring coupling and dual-homing give further options.
- MXstudio management: MXstudio gives a visual view of the network, while SNMP, RMON and LLDP support monitoring and diagnostics.
- Port and access security: Broadcast storm protection, rate limiting, access control lists, static port lock, MAC sticky, SSH, RADIUS, TACACS+ and DHCP snooping limit misuse and overload.
- Industrial protocols: EtherNet/IP, Modbus TCP and PROFINET IO Device support let automation systems work with the switch.
- Traffic control: QoS, VLANs and IGMP snooping keep priority traffic moving and limit unnecessary multicast traffic.
- Hardware-based time sync: PTP with power profiles gives precise time synchronization across devices.
EDS-4008-2GT-2GS-HV-T Specifications
| Specification | Value |
|---|---|
| Ethernet ports | 4 x 10/100BaseT(X) (RJ45) |
| Gigabit copper ports | 2 x 10/100/1000BaseT(X) (RJ45) |
| SFP slots | 2 x 100/1000BaseSFP |
| Input voltage | 110/220 VDC/VAC, single input (operating voltage 88 to 300 VDC, 85 to 264 VAC) |
| Power consumption | 11.17 W (max.) |
| Operating temperature | -40 to 75°C (-40 to 167°F) |
| Housing and IP rating | Metal housing, IP40 |
| Dimensions | 55 x 140 x 122.5 mm (2.2 x 5.51 x 4.82 in) |
| Weight | 795 g (1.75 lb) |
| MTBF | 505,936 hrs (Telcordia Standard SR-332) |
Uses in Video Monitoring, ITS and DCS Networks
MOXA names video and process monitoring, ITS, and DCS systems as uses of this range. Uses of this switch type include:
- IP Surveillance and process monitoring: Gigabit uplinks carry traffic from Fast Ethernet devices toward a scalable backbone.
- Transportation Rail/Road: Intelligent transportation systems (ITS) are a named use of the series, and the wide temperature range suits roadside and trackside cabinets.
- Automation: DCS systems benefit from ring redundancy and from EtherNet/IP, Modbus TCP, and PROFINET IO Device support.
- Power/Utility: Substation networks can use the hardware-based time synchronization and the substation listings noted below.
DIN-Rail Mounting, Terminal Blocks and DIP Switches
- Mount the switch on a DIN rail, or on a wall with the optional kit.
- Wire power through two removable 4-contact terminal blocks.
- The PWR-105-HV-I power module is pre-installed. If you replace the module, follow the specifications of the model that matches the new module.
- Use the relay alarm output (1 A @ 24 VDC) and the one digital input for alarm signaling and external signals.
- Set Turbo Ring, Master, Coupler, and Reserve with the DIP switches.
- Use the RS-232 console port (8-pin RJ45) and the reset button for local access. The LEDs show power, state, fault, ring, and time sync status.
IEC 62443-4-2, Rail, Traffic Control and Substation Listings
The switch is listed for IEC 62443-4-2 Security Level 2, which supports secure industrial network design. Rail, traffic control, and power substation environments are covered by EN 50121-4, NEMA TS2, IEC 61850-3, and IEEE 1613 Class 1. Safety and emissions listings include UL 61010-2-201, EN 62368-1 (LVD) and FCC Part 15B Class A.
Series Family and Wide-Temperature Accessories
- Product family: This switch belongs to the Moxa EDS-4008 Series, which also includes copper-only, fiber uplink, and PoE models. Choose this model when you need Gigabit copper and SFP uplinks, a high-voltage AC or DC input, and wide-temperature operation.
- Storage kits: The ABC-02-USB-T (-40 to 75°C) and ABC-03-microSD-T (-40 to 85°C) tools back up and restore configuration, support firmware upgrades, and store log files. Both are accessories sold separately.
Questions About the EDS-4008-2GT-2GS-HV-T
Does the EDS-4008-2GT-2GS-HV-T support PoE?
No. PoE ports are listed only on the EDS-4008-4P-2GT-2GS models in the series. This model has standard copper ports and does not supply power to connected devices.
Can the EDS-4008-2GT-2GS-HV-T run on both AC and DC power?
Yes. The HV power module accepts AC or DC on the same single input, so one switch fits sites with either supply.
Can the EDS-4008-2GT-2GS-HV-T connect over fiber?
Yes, through its two SFP slots. SFP modules are sold separately, and -T versions are listed for -40 to 85°C operation. Choose the module that matches the fiber type and distance of the link.
How does the EDS-4008-2GT-2GS-HV-T differ from the EDS-4008-2GT-2GS-HV?
The two share the same ports and HV power input. The difference is the operating temperature. The -T model works from -40 to 75°C, while the standard model works from -10 to 60°C.
How does the EDS-4008-2GT-2GS-HV-T differ from the EDS-4008-2GT-2GS-LV-T?
The two share the same port layout and wide temperature range. The difference is the power module. The HV-T model takes a high-voltage AC or DC input, while the LV-T model takes low-voltage DC with redundant dual inputs. ATEX, IECEx, Class I Division 2, and maritime approvals are listed for the LV-T model only.
Send an inquiry with the Enquire Now button or contact Rockford with questions about the MOXA EDS-4008-2GT-2GS-HV-T Managed Ethernet Switch in Qatar. Rockford offers pre-sales support, network design, consulting, technical support, and training. Tell us your port, power, and temperature needs, and we will help you choose a model.